Condensate pump, condensation, drain pan pump, water removal

Condensate pumps

Condensate pumps and electronic switches

SAHARA_2

SAHARA

The SAHARA is a solid state electronic condensate
removal system designed to fit neatly inside even the
smallest high wall split air conditioners or trunking.
The SAHARA’s electronic reservoir sensing unit
eliminates all worries about positioning. This versatile
little unit is so easy-going that you’re spoilt for choice.

Technical Data:
Power supply: 120/240 V, 50/60 Hz Auto sensing
Power consumption: 16 W max., 0.25 when idle
Alarm relay: 5 A, 30 VDC, 250 VAC Break
on fault
Capacity: 12 litres/hour max. (3.17 US gal/h)
Discharge head: >20 m (65 ft) vertical, >100 m (328 ft) horizontal
1 m max. (3.28 ft) suction
Ambient temp: 0° C - 40° C (32° F to 104° F)
Material: Flame retardant ABS - UL94 5 VA
Discharge tube: 6 mm (1/4“) ID
Supply cable lenght: 1.5 m, (5 ft)
Pump-sensor-tube: Lenght 5 ft, dia. 3.3 mm (1/8“)
Dimensions pump: 135 x 46 x 32 mm (5.3“ x 1.8“ x 1.26“)
Dimensions sensor: 45 x 36 mm dia. (1.8“ x 1.4“ dia.)
Noise level:  ≤ 16 dB

Part No 4678482

Download:
> Instruction manual > Installation Video


KAROO_2

KAROO

The KAROO drain pan pump is a submersible condensate removal pump
designed to automatically remove condensate water
from refrigerated cases, dehumidifi ers, fan coils and
air conditioning systems. The pump is intended to be
installed within a collection tray inside the equipment.
The water level is measured by an Electronic Energy
Control System (EECS) that controls the operation ofthe pump via the fully-encapsulated circuitry.
Technical Data:
Power supply:  120/240 V, 50/60 Hz Auto sensing
Power consumption: 16 W max., 0.25 when idle
Alarm relay:  5 A, 30 VDC,250 VAC Break
on fault 
Capacity:
12 litres/h max. (3.17 US gal/h)
Discharge head:  >20 m (65 ft) vertical, >100 m (328 ft)
horizontal
1 m max. (3.28 ft) suction
Ambient temp: 0° C - 40° C (32° F to 104° F)
Material: Flame retardant ABS - UL94 5 VA
Discharge tube: 6 mm (1/4“) ID
Dimensions: 160 x 43 x 34 mm (6.3“ x 1.7“ x 1.3“)
Noise level:  ≤ 12 dB
Part No 4678512

Download:
> Instruction manual > Installation Video

YUMA_2

YUMA

The YUMA condensate pump is easy to fit and easy to maintain – the pump is made for installers.
Speedy fi tting is assured with the YUMA. Completely
automatic operation is enhanced by the intelligent
Electronic Energy Control System (EECS) circuitry to
guarantee quiet starting and stopping, as well as power control to regulate the amount of energy required to remove the condensate.

Technical Data:
Power supply:   120/240 V, 50/60 Hz Auto sensing
Power consumption:  16 W max., 0.25 when idle
Alarm relay: 5 A, 30 VDC, 250 VAC Break on fault
Capacity:  12 litres/hour max. (3.17 US gal/h)
Discharge head:   >20 m (65 ft) vertical, >100 m (328 ft)
horizontal, 1 m max. (3.28 ft) suction 
Ambient temp:  0° C - 40° C (32° F to 104° F)
Material:  Flame retardant ABS - UL94 5 VA
Discharge tube: 6 mm (1/4“) ID
 Dimensions: 175 x 46 x 40 mm (6.9“ x 1.8“ x 1.6“)
Noise level:  ≤  18 dB
 
Part No 4678520

Download:
> Instruction manual > Installation Video
gobi_220_01

GOBI

The GOBI is a condensate discharge module designed to be fitted below modern wall mounted airconditioners. The new design and technology makes the GOBI our most innovative water sensing system ever. The GOBI pump incorporates the Electronic Energy Control System (EECS), microprocessor control delivers a smooth unobtrusive pump operation.

Technical Data:
Power supply: 120/240Vac, 50/60Hz Auto sensing
Power consumption: 16W max., 0.25W when idle
Alarm relay: 5A, 30Vdc, 250Vac Break on fault
Capacity:
12 litres/hour max. (3.17 US gal/h)
Maximum head: Vertical >20m (65 ft), Horizontal >100 (328 ft)
Suction 1 m max. (3.28 ft)
Ambient temp: 0 - 40°C
Water temp: 25°C max.
Material: Flame retardant ABS  UL94 5VA
Discharge tube: 6mm (1/4”) ID
Dimensions: 286 x 61 x 53mm (11.3” x 2.4” x 2”)
Noise level:  ≤  21 dB

Part No 4678538

Download:
> Instruction manual   > Installation video


 

Electronic switches

LAC-EXTREME

LAC EXTREME

The LAC EXTREME is a Low Ambient Controller for all air cooled condensing units in air conditioning and refrigeration units with fan motor.

The intelligent logic programmed into these high specification controllers decides the correct speed for the outdoor fan, whether the fan should stop and for how long, to provide the maximum system efficiency.

Technical Data:
Fan motor running current:  4 A max.
Ambient temperature:  -30 °C to +50 °C
Set point condensing temperature range:  +30 °C to +60 °C
Input voltage from reversing valve:  24 - 240 V, 60 Hz

Part No 4678563

Download:
> Instruction manual


LAC UNIVERSAL

The LAC Universal is an electronic controller for outdoor fans on heat pumps and cooling-only air conditioners. By controlling the speed of the fan in changing ambient temperatures this electronic controller brings benefits to all air conditioning installations.
Technical Data:
Max continuous fan motor current:  2 A
Max. fan motor start current:  5 A
Controller max ambient temperature:  50 °C
Condensing temperature control range:  30 °C to 60 °C
Fan minimum speed adjustment range:  0–100%
Heat pump solenoid valve voltage:  24–250 V AC

Part No 4678555

Download:
> Instruction manual


AQUASWITCH

AQUASWITCH

The AQUASWITCH is an electronic water switch for valves, pumps and alarms. The AQUASWITCH is a small controller with a sensitive electronic circuit encapsulated inside. Constructed for all applications where a reliable switch is needed to control or indicate the presence of water.

Technical Data:
Voltage:  95 – 254 V, 50 Hz
  24 V AC/DC
Max. switched relay current:  5 A
Relay switch-off delay:  2.5 +/- 0.5 seconds
Ambient temperaturerange:  0 °C to 75 °C
Water level for switching relay:  0 +/- 1/5"
(depends on water quality)

AQUASWITCH

95-254 V, 50 Hz
Part No 4678741

AQUASWITCH-24

24 V AC/DC
Part No 4678546


Download:
> Instruction manual


 

INVERTER_CHECK_KIT

INVERTER_CHECK_KIT_inkl_alle_Kabel

INVERTER CHECK KIT

The inverter check kit is an invaluable test kit for the analysis of problems solving with inverted-fed air conditioners.

Designed to be used both in installation and maintenance, this kit can indicate correctly-operating inverter power stages, as well as the serial-link communication between the condensing unit and the indoor units. This allows the air conditioning engineer to easily identify faults and reduces the time required for analysis and repair.

The kit contains the electronic module with a set of leads for testing the serial communications links, as well as a selection of cables and connectors for the power output terminals of the inverter.

Part No 4678571

Download: > Instruction manual


 

Accessories


IN-LINE_FILTER

IN-LINE FILTER

The IN-LINE FILTER fits in the drain line from an air conditioner to its condensate pump, and should be used wherever dirt particles, construction debris, hairs or greasy deposits can be washed from the drain tray down into the pump.

Part No 4678597

Download: > Instruction manual

Messbereich: Atm. bis 50 Mikron = 0,06 mb